FIRE INPUT ALARM CONDITION — This configuration
defines the condition of the Fire Shutdown input point that will
generate an alarm and turn off the fan. If set to Normal (for nor-
mally open contact), the alarm condition will occur when the
contact is closed. If set to Invert (for normally closed contact),
the alarm condition will occur when the contact opens.
Fire Inp Alm
Conditn: Range Invert/Normal
Default Value Normal
Controller Identification Screen — The controller
identification screen contains reference information used to
identify the PremierLink™ controller. See Table 14.
DESCRIPTION The Description point displays the type of
device.
LOCATION The Location point shows the location of the
device.
SOFTWARE PART NUMBER — The Software Part Num-
ber indicates the part number of the software being used.
MODEL NUMBER — The Model Number indicates the
model number of the device being used.
SERIAL NUMBER The Serial Number indicates the serial
number of the device being used.
REFERENCE NUMBER — The Reference Number indi-
cates the version of the software being used.
Table 14 — Controller Identification
Holiday Configuration Screen — The Holiday Con-
figuration screen is used by the PremierLink controller to store
configuration fields for up to 12 holidays. See Table 15.
START MONTH The Start Month field is used to config-
ure the month that the holiday will start. The numbers 1
through 12 are used to indicate which month is specified.
Start Month: Range 1 to 12
Default Value 1 (January)
START DAY The Start Day field is used to determine
which day the holiday will start.
Start Day: Range 1 to 31
Default Value 1
DURATION The Duration field indicates how long the
holiday will last (in days).
Duration: Range 0 to 365
Default Value 0
As an example, if a Holiday is configured for Month 2,
Day 5, Duration 2, then the Holiday will start February 5 and
end February 7.
Table 15 — Holiday Configuration
Occupancy Configuration Screen — The Occu-
pancy Configuration Screen is used to configure the occupancy
schedule for the PremierLink controller. Occupancy schedule
OCCPC64 is used by the controller for heating and cooling.
Occupancy schedule OCCPC63 is only used by the
H3_EX_RV output when it is configured for type 6 Occupied
Schedule. See Table 16.
MANUAL OVERRIDE HOURS — The Manual Override
Hours point is used to command a timed override by entering
the number of hours the override will be in effect. If the occu-
pancy schedule is occupied when this number is downloaded,
the current occupancy period will be extended by the number
of hours downloaded.
If the current occupancy period is unoccupied when the
occupancy override is initiated, the mode will change to occu-
pied for the duration of the number of hours downloaded. If the
occupancy override is due to end after the start of the next
occupancy period, the mode will transition from occupancy
override to occupied without becoming unoccupied and the
occupancy override timer will be reset.
An active occupancy override or a pending occupancy
override may be canceled by downloading a zero to this
configuration. Once a number other than zero has been down-
loaded to this configuration, any subsequent downloads of any
value other than zero will be ignored by the controller.
Manual Override
Hours: Units hours
Range 0 to 4
Default Value 0
OCCUPANCY SCHEDULE For flexibility of scheduling,
the occupancy programming is broken into 8 separate periods.
DESCRIPTION VALUE UNITS STATUS FORCE NAME
Y1 - Call for Cool 1 On Y1
Y2 - Call for Cool 2 On Y2
W1 - Call for Heat 1 Off W1
W2 - Call for Heat 2 Off W2
G - Call for Fan On G
DESCRIPTION VALUE UNITS NAME
Alarm Control
Alarm Routing Control 00000000 ALRMCNT
Realarm Time 0 min REALARM
Control Temp Hysteresis 5.0 ^F SPTHYS
Control Humid Hysteresis 5 %RHHYS
Supply Air Temperature
Low Limit 45.0 dF LOWLIM
High Limit 150.0 dF HIGHLIM
IAQ High Alert Limit
Low Limit 0.0 LOWLIM
High Limit 1200.0 HIGHLIM
Fire Inp Alm Conditn Normal FIAC
DESCRIPTION VALUE UNITS NAME
Description: Rooftop Control DevDesc
Location: Location
Software Part Number: CESR131269-08 PartNum
Model Number: ModelNum
Serial Number: SerialNo
Reference Number: Version 2.000 RefNum
DESCRIPTION VALUE UNITS NAME
Start Month 1 MONTH
Start Day 1 DAY
Duration 0 DURATION