Carrier 33ZCVAVTRM Specifications Page 190

  • Download
  • Add to my manuals
  • Print
  • Page
    / 316
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 189
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
New Pg 4 Catalog No. 523-330 Printed in U.S.A. PC 111 Form 33CS-19PS
Replaces: New
Book 1 4
Ta b 1 1 a 1 3 a
Carrier Corporation • Syracuse, New York 13221 3-01
Book 1
Ta b C S 1
The 33ZCT55SPT (T55) space temperature sensor
with override button is required for all applications. The
space temperature sensor monitors room temperature
which is used by the PremierLink controller to deter-
mine the temperature of conditioned air that is allowed
into the space.
Space temperature sensor with override button
and set point adjustment —
The 33ZCT56SPT
(T56) space temperature sensor with override button
and set point adjustment can be used in place of the
33ZCT55SPT (T55) space temperature sensor if local
set point adjustment is required. The space temperature
sensor monitors room temperature which is used by the
PremierLink controller to determine the temperature of
conditioned air that is allowed into the space.
T58 communicating sensor with override button,
set point adjustment, and manual fan control —
The 33ZCT58SPT (T58) communicating room sensor
with override button, set point adjustment, and manual
fan control can be used in place of the 33ZCT55SPT
space temperature sensor.
The T58 communicating
room sensor measures and maintains room temperature
by communicating with the controller.
CO
2
sensor
Three different CO
2
sensors are avail-
able for monitoring space indoor-air quality.
The 33ZCSENCO2 sensor is an indoor, wall mounted
sensor with an LED (light-emitting diode) display. The
sensor has an analog output (0 to 10 vdc or 4 to 20 mA)
over a range of 0 to 2000 ppm. An SPDT contact
is provided to close at 1000 ppm with a hysteresis of
50 ppm.
The 33ZCT55CO2 sensor is an indoor, wall mounted
sensor without display. The CO
2
sensor also includes a
space temperature sensor with override button.
The 33ZCT56CO2 sensor is an indoor, wall mounted
sensor without display. The CO
2
sensor also includes a
space temperature sensor with override button and tem-
perature offset.
Linkage thermostat —
The Linkage Thermostat
(33CSKITLST-01) is used to control multiple units from
a single thermostat. The Linkage Thermostat can con-
trol up to 8 units. It is used in place of any space
temperature sensor.
Dimensions
Accessories (cont)
Page view 189
1 2 ... 185 186 187 188 189 190 191 192 193 194 195 ... 315 316

Comments to this Manuals

No comments