Carrier 33ZCVAVTRM Specifications Page 262

  • Download
  • Add to my manuals
  • Print
  • Page
    / 316
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 261
2
Generic PID Control
Time Scheduling with/without Override
Analog Temperature Control
•Discrete Interlock
Discrete Staging Control
Permissive Interlock
Nighttime Free Cooling
Set Point Reset
Optimal Start/Stop
Linkage to airside systems
8 inputs
Each input (1 to 8) can be used as a discrete, analog, or
temperature input
Discrete inputs can be dry contact or pulsed dry contact
Analog inputs can be 4 to 20 mA or 0 to 10 vdc
Temperature inputs can be 5K or 10K ohm thermistors
8 outputs
Each output (1 to 8) can be discrete or analog
Discrete outputs are 24 vdc at 80 mA
Analog outputs are 4 to 20 mA or 0 to 10 vdc (varies
with point type)
Carrier network features
When included in a network with other network control-
lers, Option Modules, and user interfaces, the following
additional capabilities are possible:
Alarm processing, messages, and annunciation
Runtime, history, and consumable data collection and
report generation
Demand limiting
Broadcast of data such as outside-air temperature, out-
side air humidity, and time of day
Timed overrides for use with Tenant Billing
•Airside linkage
Enclosure and power supply
The Universal Controller is designed so that it can be easily
installed in a field-supplied enclosure (not outdoor rated).
The Universal Controller uses any standard, Class II, SELV-
compatible, field-supplied 24 vac, 60 va transformer.
Specifications
Power Requirements. . . . . . . . . . .60 va at 24 vac ± 15%
(1.5a at 33 vdc ± 15%)
Dimensions . . . . . . . . . . . . 14-in. H x 6.5-in. W x 2-in. D
(35.5 cm x 16.5 cm x 5.1 cm)
Operating Temperature. . . –40 F to 158 F, Outdoor Rated
(–40 C to 70 C)
Storage Temperature . . . .–40 F to 185 F (–40 C to 85 C)
Operating Humidity . . . . . . . 10 to 95%, non-condensing
Discrete output specifications
Output Signal. . . . . . . . . . . . . . . . . . . . 24 vdc at 80 mA
Analog output specifications
4 to 20 mA Type
Load Resistance . . . . . . . . . . . . . . . . . 500 to 600 ohms
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . .0.04 mA
Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .±2%
0 to 10 vdc Type (varies with point type)
Load Resistance . . . . . . . . . . . . . . . . . . . . . . . .50 ohms
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 mV
Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .±2%
Discrete input specifications
Dry Contacts . . . . . . . . . . . . . . . . . . . . . Switch Closure
Pulsing Dry Contacts
Repetition Rate . . . . . . . . . . . . . . . . . . . . . . .5 Hz max.
Minimum Pulse Width . . . . . . . . . . . . . . . . . . . 100 msec
Analog input specifications
4 to 20 mA Type
Wire type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-wire
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . .0.025 mA
Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1.5%
0 to 10 vdc Type
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.0125 V
Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1%
5K Thermistor Type
Nominal reading at 5,000 ohms. . . . . . . . . . . 77 F (25 C)
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.2 F
Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . + 1 F
10K Thermistor Type
Nominal reading at 10,000 ohms. . . . . . . . . . 77 F (25 C)
Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.2 F
Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . + 1 F
Approvals
The Universal Controller is UL 873 and CE Mark Industrial
listed.