System Pilot Maintenance Table — The System
Pilot Maintenance Table (SP_MAINT) displays the mode of
the controller, the controlling set point, the current space tem-
perature, and occupancy status of the PremierLink™ control-
ler. It also displays PremierLink controllers occupied and un-
occupied heat and cool set points which the user may change
from this table. See Table 22. This screen can be accessed
through the maintenance option on the System Pilot™ device
or through Carrier network software.
Table 22 — System Pilot Maintenance Table
(SP_MAINT)
ROOFTOP MODE This variable will display the current
operating mode of the controller. The variable will be displayed
in the attached System Pilot device’s default display.
Rooftop Mode: Display Range OFF, COOL, HEAT,
FAN ONLY,
UNOCCOOL,
UNOCHEAT,
WA R M U P,
FREECOOL,
PRESS, EVAC
Network Access Read only
CONTROL SET POINT — This variable will display the
current controlling set point of the controller. This variable is
not displayed in the System Pilot default display.
Control
Setpoint: Display Units degrees F (degrees C)
Display Range: 40.0 to 99.9
Network Access Read only
LINKAGE MASTER — This is not used.
Linkage
Master: Display Range No/Yes
Network Access Read Only
SPACE TEMPERATURE This variable is the current
space temperature of the PremierLink controller. The variable
will be displayed in the attached System Pilot device’s default
display.
Space
Temperature: Display Units degrees F (degrees C)
Display Range –40.0 to 245.0
Network Access Read/Write
OCCUPIED This variable displays whether the controller
is operating in the occupied mode. The variable will be dis-
played in the attached System Pilot device’s default display.
Occupied: Display Range No/Yes
Network Access Read Only
OCCUPIED HEAT SET POINT — This variable displays
the occupied heat set and will be displayed in the attached
System Pilot device’s default display if the PremierLink con-
troller is in the occupied mode.
Occupied
Heat Set Point: Display Units degrees F (degrees C)
Display Range 40.0 to 90.0
Network Access Read/Write
OCCUPIED COOL SET POINT — This variable displays
the occupied cool set point and will be displayed in the at-
tached System Pilot device’s default display if the PremierLink
controller is in the occupied mode.
Occupied
Cool Set Point: Display Units degrees F (degrees C)
Display Range 45.0 to 99.9
Network Access Read/Write
UNOCCUPIED HEAT SET POINT — This variable dis-
plays the unoccupied heat set point and will be displayed in the
attached System Pilot device’s default display if the Premier-
Link controller is in the unoccupied mode.
Unoccupied
Heat Set Point: Display Units degrees F (degrees C)
Display Range 40.0 to 90.0
Network Access Read/Write
UNOCCUPIED COOL SET POINT — This variable dis-
plays the unoccupied cool set point and will be displayed in the
attached System Pilot device’s default display if the Premier-
Link controller is in the unoccupied mode.
Occupied
Cool Set Point: Display Units degrees F (degrees C)
Display Range 45.0 to 99.9
Network Access Read/Write
System Pilot Alternate Maintenance Table —
The System Pilot Alternate Maintenance Table (ALT_DISP)
displays the current supply air temperature, heating and cool-
ing capacity and other information listed in the table. See
Table 23.
Table 23 — System Pilot Alternate Maintenance
Display Table(ALT_DISP)
NOTE: This screen can be viewed using the System Pilot
when attached to the PremierLink controller. To view this
screen, press the right button on the System Pilot device for
5 seconds while at the default display. This screen can also be
viewed using Carrier network software.
SUPPLY AIR TEMPERATURE — The Supply Air Temper-
ature point displays the temperature of the air leaving the unit
located downstream of any cool or heat sources. This sensor is
required for proper function of the heating, cooling, and econo-
mizer systems.
Supply Air
Temperature: Display Units F (C)
Display Range –40.0 to 245.0
Network Access Read/Write
DESCRIPTION VALUE UNITS NAME
Rooftop Mode
COOL MODE
Control Setpoint
70 dF CLSP
Linkage Master
No LINKMAST
Space Temperature
73 dF SPT
Occupied
Ye s Z O N E O C C
Occupied Heat Setpoint
70 dF OHSP
Occupied Cool Setpoint
74 dF OCSP
Unoccupied Heat Setpoint
69 dF UHSP
Unoccupied Cool Setpoint
75 dF UCSP
DESCRIPTION VALUE UNITS NAME
Supply Air Temperature
66.5 dF SAT
Cooling % Total Capacity
0 % CCAP
Heating % Total Capacity
0 % HCAP
Outdoor Air Temperature
74.8 dF OAT
Enthalpy
Low ENTH
Economizer Position
20 % ECONOS
Indoor Air Quality
0 IAQI
Filter Status
Clean FLTS
Indoor RH
0 %IRH
Page view 173