Carrier 33ZCVAVTRM Specifications Page 2

  • Download
  • Add to my manuals
  • Print
  • Page
    / 316
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 1
2
capable of local set point
adjustment with field-installed
temperature sensor (with
temperature offset)
both controller housing and actuator
are UL94-5V plenum rated
Features/Benefits
Flexibility for every application
The zone controller is a single duct, fan
powered, variable air volume (VAV)
terminal control with a factory-
integrated controller and actuator.
The zone controller maintains precise
temperature control in the space by
operating the terminal fan and regulat-
ing the flow of conditioned air into the
space.
Buildings with diverse loading
conditions can be supported by con-
trolling reheat (single duct only) or
supplemental heat. The zone controller
can support single position hot water,
modulating hot water, 2-stage electric,
or perimeter heat.
Carrier Linkage System
compatibility
When linked to a Carrier Linkage
System, the zone controller provides
numerous features and benefits such as
weighted average demand for system
operation, intelligent supply-air
temperature reset, set point averaging,
global set point schedule, and occu-
pancy scheduling. Duct static reset for
the air source is provided, based on
terminal requirements.
Additional control features
The zone controller provides additional
control features such as Occupied/
Unoccupied scheduling initialized via
the network. The zone controller offers
override invoked from a wall sensor
during unoccupied hours from 1 to
1440 minutes in 1-minute increments.
Optional Indoor Air Quality (IAQ) or
relative humidity monitoring and con-
trol are also available.
Simple actuator connection
The zone controller control assembly
contains an integral VAV actuator
assembly that is field mounted to the
VAV terminal damper shaft, similar to
the mounting of a standard actuator.
The actuator is rated at 35 lb.-in.
(3.95 N-m) torque, a 90-degree stroke,
and provides second nominal timing at
60 Hz. The actuator is suitable for
mounting onto a
3
/
8
-in. (9.5 mm)
square or round VAV box damper
shaft, or onto a
1
/
2
-in. (13 mm) round
damper shaft. The minimum VAV
box damper shaft length is 1
3
/
4
-in.
(45 mm). The zone controller is
designed for vertical or horizontal
mounting.
Ease of installation
The zone controller is provided with
removable connectors for power and
communications. The zone controller
has non-removable screw type connec-
tors for inputs. The removable connec-
tors are designed so that they can be
inserted one way so as to prevent
installation errors. The zone controller
also provides an RJ-14 modular phone
jack for the Network Service tool
connection to the module via the
Carrier Comfort Network (CCN)
communications.
An optional Conduit Box Cover
(Part Number 33ZCCONBOX)
provides for field wiring connection via
conduit. The conduit box is designed
to accept two
1
/
2
-in. (13 mm) EMT
conduits.
User Interface
The 33ZCVAVTRM is designed to
allow a service person or building
owner to configure and operate the
unit through the CCN user interfaces.
A user interface is not required for day-
to-day operation. All maintenance,
configuration, setup, and diagnostic
information is available through the
Level II communications port to allow
data access by an attached computer
running Network Service Tool,
ComfortVIEW
, or ComfortWORKS
®
software.