Carrier 33ZCVAVTRM Specifications Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 316
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
3
Specifications
Wiring connections
Field wiring is 18 to 22 AWG (American Wire Gage). The
zone controller is a NEC (National Electronic Code) Class 2
rated device.
Inputs
space temperature sensor
primary air damper position
airflow sensor (factory installed)
field-installed remote wall sensor set point adjustment
optional supply temperature sensor (required for heat
and supply air monitoring)
optional primary air temperature sensor (required for sys-
tems which do not utilize a linkage compatible air source)
optional IAQ sensor
optional relative humidity sensor
Outputs
internally factory-wired VAV actuator
heating
- modulating (floating) heat
- up to 2 stages of heat
- single position heat
Power supply
The power supply is 24 VAC ± 10% at 40 VA
(50/60 Hz).
Power consumption
The power requirement sizing allows for accessory water
valves and for the fan contactor. Water valves are limited to
15 VA on both single-position and modulating hot water.
The fan contactor is limited to 10 VA (holding) each.
Accuracy
Terminal airflow (nominal cfm) is rated at 1-in. wg
(249 kPa) measured velocity pressure. The zone controller
is capable of controlling to as low as 10% or as high as
125% of nominal airflow with an accuracy of ± 3% (nomi-
nal) at any point within the range.
Hardware (memory)
FLASH EPROM
Differential pressure range
0 to 2.0 in. wg (0 to 498 kPa) maximum for the onboard
flow sensor.
Specified sensing temperature range
The zone controller space temperature range is –40 to
245 F (–40 to 118 C). The zone controller has an allow-
able control set point range from 40 to 90 F (4 to 32 C) for
heating and 45 to 99 F (7 to 37 C) for cooling.
Communications
The number of controllers is limited to 128 zones maxi-
mum, with a limit of 8 systems (Linkage Coordinator con-
figured for at least 2 zones). Bus length may not exceed
4000 ft (1219 m), with no more than 60 devices on any
1000 ft (305 m) section. Optically isolated RS-485 repeat-
ers are required every 1000 ft (305 m).
At 19,200 and 38,400 baud, the number of controllers
is limited to 128 maximum, with no limit on the number of
Linkage Coordinators. Bus length may not exceed 1000 ft
(305 m).
Environmental ratings
Operating Temperature: 32 to 140 F (0° to 60 C) at 0 to
90% RH (non–condensing)
Shipping Temperature: –40 to 185 F (-40 to 85 C) at 0 to
90% RH (non–condensing)
Vibration
Performance vibration:
0.014-in. (0.356 mm) Peak-to-Peak displacement
measured at 5 to 31 Hz
0.75 G measured at 31 to 300 Hz
Corrosion
Office environment. Indoor use only.
Approvals
listed under UL 916-PAZX and UL 873
conforms to requirements per European Consortium
standards EN50081-1 (CISPR 22, Class B) and
EN50082-1 (IEC 801-2, IEC 801-3, and IEC 801-4) for
CE mark labeling
UL94-5V plenum rated (housing and actuator)
Accessories
Conduit box — The 33ZCCONBOX conduit box pro-
vides two conduit connections to the zone controller for
installations requiring the use of conduit due to local electri-
cal codes.
Supply air temperature sensor — The 33ZCSENSAT
supply air temperature sensor is required for heating appli-
cations or stand-alone operation. The sensor is optional on
cooling only applications and is used for supply air moni-
toring. The sensor has an operating range of –40 to 245 F
(–40 to 118 C).
Primary air temperature sensor — The 33ZCSENPAT
primary air temperature sensor is required on a linkage
coordinator zone controller if the zone controller is not
using a CCN linkage compatible air source. The sensor is
used to monitor the equipment’s supply-air temperature.
The temperature is broadcast to the zone controllers which
receive information from the linkage coordinator. The
sensor has an operating range of –40 to 245 F (–40 to
118 C).
Space temperature sensor with override button —
The 33ZCT55SPT space temperature sensor with over-
ride button is required for all applications. The space tem-
perature sensor monitors room temperature which is used
by the zone controller to determine the amount of condi-
tioned air that is allowed into the space.